REFUsol 20K-2T (853P020.200)
User manual
- 47 -
The function is divided into three options: CTR Totalpower, CTR Phasepower
and CTR SellingPower, the first one is the default usage for REFUsol 20K-2T. Refer
to <7.5 Smart meter usage in this manual for specific operation methods.
15. OVP
Set the over voltage protection value. The factory default of this value is to
meet the local safety requirements. If you need to reset it, you must strictly comply
with the local safety requirements.
16. Power Limit
Set the Power Limit percent value.
17. Reactive Para
Set the Reactive Para enable/disable.
18. Hard Reflux
Set the Hard Reflux enable/disable. After hard countercurrent prevention is
enabled, set the hard countercurrent power percentage.
19. Set Insulation
Set the Insulation enable/disable. Set the insulation impedance after the
function is enabled.
20. PELineControl
Set the PE Line Control enable/disable.
21. InputSafety
Long press the key to enter the current menu, put the required safety files
into the U disk specified folder, insert the U disk, select Enable import safety files.
22. Set Safety
Long press the key to enter the current menu, if no safety files is imported,
"none" will be displayed. It is necessary to import the safety files first. After
importing the safety files, you can switch safety standards according to the
operation prompts.
23. Autotest Fast
18.Autotest
Fast
OK
Start Autotest
Long press the to start
Testing 59.S1...