If it occurs frequently, please check
whether the grid voltage and grid
frequency are within the allowable
range of the inverter; if not, please
contact the customer service of REFU
ELEKTRONIK; if yes, please check
whether the connection between the
circuit breaker at the AC side and the
output cable is normal; if the grid
voltage and grid frequency are within
the allowable range of the inverter,
and the AC side wiring is confirmed
to be correct, the alarm still appears
frequently With the approval of the
local power operator, please contact
the customer service of new energy
of Capital Airlines to modify the
protection points of over / under
voltage and over / under frequency
of inverter grid.
There are internal faults of inverter,
turn OFF the “DC switch”, wait for 5
minutes, then turn ON the “DC
switch”. Check whether the fault is
rectified. If no, please contact
technical support.