REFUsol 20K-2T (853P020.200)
User manual
- 65 -
disconnect the DC switch of the
inverter, wait for 5 minutes, and then
turn on the DC switch. Observe
whether the fault has been
eliminated after the inverter is
restarted. If not, please contact the
customer service of REFU
ELEKTRONIK.
ID162
RemoteShutdow
n
RemoteShutdown
ID163
Drms0Shutdown
Drms0 shunt
down
ID165
RemoteDerating
RemoteDerating
Inverter shows ID83 when remote
derating. If no one operate this
function, please check the
connection (I/O) according to chapter
4.5
ID166
LogicInterfaceDe
rating
Logical interface
derating
ID167
AlarmAntiRefluxi
ng
Anti Refluxing
derating
ID169
FanFault1
Fan 1 Alarm
Check whether the inverter has dust
and dust, whether there are foreign
matters blocking the fan at the air
inlet. If so, please improve the
ventilation and heat dissipation of
the environment. It is recommended
that the inverter should be cleaned
once every half a year.
ID170
FanFault2
Fan 2 Alarm
ID171
FanFault3
Fan 3 Alarm
ID172
FanFault4
Fan 4 Alarm
ID173
FanFault5
Fan 5 Alarm
ID174
FanFault6
Fan 6 Alarm
ID177
Reserved
Reserved
ID178
Reserved
Reserved
ID179
Reserved
Reserved
ID180
Reserved
Reserved
ID181
Reserved
Reserved
ID182
Reserved
Reserved
ID193-
ID224
StringFuse_Fault
0-31
String fuse open
circuit alarm
There are internal faults of inverter,
turn OFF the “DC switch”, wait for 5
minutes, then turn ON the DC
switch”. Check whether the fault is
rectified. If no, please contact
technical support.