12 SP 1, SP 2, SP 2.3, SP 2.4
SPR1, SPR 2, SPR 2.3, SPR 2.4
Input control signals - analogue: .................................................................................................. 0 - 20 mA
................................................................................................................................................. 4 - 20 mA
.................................................................................................................................................... 0 - 10 V
Input resistance for signal 0/4 - 20 mA.................................................................................................250
Input resistance for signal 0/2 - 10 V................................................................................................... 50k
(Actuator opens at rising of control signal.)
Controller linearity: ............................................................................................................................. 0.5 %
Controller insensitiveness: ........................................................................................... 1 - 10% (adjustable)
Feedback (position transmitter): ...................................................................... resistive 100 up to 10,000 Ω
............................................................................................................................... current 4 up to 20 mA
Power outputs: ............................................................................................................ 2x relay 5A/250 V AC
Digital outputs: ............4x LED (supply, error, adjustment, "opening", "closing" - with two-colour LED)
Error status: .................................................................................................. control switch 24 V, 2W - POR
Reaction at error situation: transmitter error - error message LED
Control signal missing: .................................................................................................. error message LED
SYS mode: ...................................................................................................................... error message LED
Adjusters: .............................................................................................................. communication connector
........................................................................................................... 2x calibrating and adjusting button
Manual control: ..................... with handwheel;
rotating clockwisely (counter-clockwisely ) EA output part is moving in direction "Z" ("O")
Local position indication ................................... with position indicator visible through aperture in upper cover
2.2.1 Mechanical connection
Basic and connecting dimensions are given in dimensional drawings.
2.2.2 Electric connection
with terminal board (X): ...max. 24 terminals
connecting cable size max. 1.5 mm
2
(SP 1, SPR 1- 2.4),
or 2.5 mm
2
(SP 2 -2.4)
3 cable glands - cable diameter from 3,5 to 5mm, 6 to 10.5mm and 8 to 14,5mm SP(R) 1
3 cable glands 2x cable diameter from 6 to 10,5mm and 1x 8 to 14,5 mm SP(R) 2 SP(R) 2.4
with connector (XC): ........max. 32 terminals
connecting cable size max. 0.5 mm
2
2 cable glands, cable diameter 1x from 12,5 to 19 mm and 1x from 8 to 14,5 mm
with protection terminal:
external and internal, mutually connected and marked with protection earthling mark
Electric connection: according to wiring diagrams.