ST 0, STR 0 9
Electronic position controller (N)
Controller software equipment:
A) Function and parameters
programmable functions:
..with functional buttons SW1, SW2 and LED diodes D1, D4 directly placed on controller
..with computer or terminal equipped with corresponding programme, using RS 232 interface.
programmable parameters:
..control signal
..response to SYS-TEST signal
..mirroring (ascending/descending characteristics)
..insensitiveness
..EA limit positions (only with computer and ZP2 programme)
..way of regulation
B) Operation states of controller
Error message from error memory: (using LED diodes and RS 232 and personal computer)
..control signal missing or faulty
.. input value of current control signal under 3.5 mA
..existence of SYS-TEST signal
..activity of switches
..failure of feedback position transmitter
Statistic data: (using RS 232 and personal computer)
..number of controller operation hours
..frequency of relay switching in direction "opening"
..frequency of relay switching in direction "closing"
Supply voltage: ................................................................ terminal 61 (L1) -1(N) - 230 V AC, ±10%
Frequency: ................................................................................................................ 50/60 Hz ±2%
Input control signals - analogue: .................................................................................... 0 - 20 mA
..................................................................................................................................... 4 - 20 mA
........................................................................................................................................ 0 - 10 V
Input resistance for signal 0/4 - 20 mA......................................................................................250
Input resistance for signal 0/2 - 10 V........................................................................................ 50k
(Actuator opens at rising of control signal.)
Controller linearity: ................................................................................................................ 0.5 %
Controller insensitiveness: ............................................................................ 1 - 10% (adjustable)
Feedback (position transmitter): ........................................................ resistive 100 up to 10,000 Ω
.................................................................................................................. current 4 up to 20 mA
Power outputs: .............................................................................................. 2x relay 5A/250 V AC
Digital outputs: ........4x LED (supply, error, adjustment, "opening", "closing" - with two-colour LED)
Error status: .................................................................................... control switch 24 V, 2W - POR
Reaction at error situation: ................................................. transmitter error - error message LED
Control signal missing: ................................................................................... error message LED
SYS mode: ........................................................................................................ error message LED
Adjusters: ................................................................................................ communication connector
.............................................................................................. 2x calibrating and adjusting button
Switching-off:
Switching-off voltage: ................ 250 V(AC); 50/60 Hz; 2 A; cos ϕ=0.8; or 250V(DC); 0,1 A,
............................................ or 24 V (DC); 2 A; T=L/R=3ms
Manual control: ............................................................................................................... with handle;
rotating clockwisely (counter-clockwisely) EA output part is moving in direction "Z" ("O")
Output part backlash: ....................................................... max. 0,25 mm (at 5% of max. load thrust)