EasyManuals Logo

Regin ALD24A1 User Manual

Regin ALD24A1
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
3930-D JAN 07
ALD24A1
Box 116
428 22 KÅLLERED SWEDEN
Tel +46 (0)31 720 02 00 Fax +46 (0)31 720 02 50
Configuration
All settings, apart from choosing internal or external sensor, are
made using the four buttons on the front. To access the con-
figuration menu, simultaneously depress and hold the two arrow-
buttons. After a few seconds the display will show 00
0. Now
release the arrow-buttons and klick the minus-button three times
in rapid succession. The display will show the first menu-page.
Move through the menu pages using the arrow-buttons. Change
parameter values using the + and - buttons.
To exit the configuration menu, simultaneously click the two arrow-
buttons. The ALD24A1 will also automatically exit the menu system
after a few minutes of button inactivity.
Menu listing (FS = Factory settings)
SETP HEATING Setpoint heating. Range 0...30°C in 0.5K
increments. (FS = 21.0°C)
If presence detection is activated (see below) two heating setpoint
settings will be shown.
SETP HEATING Setpoint heating, occupied. Range 0...30°C in
0.5K increments. (FS = 21.0°C)
SETP HEATING Setpoint heating, unoccupied. Range 0...30°C in
0.5K increments. (FS = 17.0°C)
SETP COOLING Setpoint cooling. Range 0...30°C in 0.5K
increments. (FS = 24.0°C)
If presence detection is activated (see below) two cooling setpoint
settings will be shown.
SETP COOLING Setpoint cooling, occupied. Range 0...30°C in
0.5K increments. (FS = 24.0°C)
SETP COOLING Setpoint cooling, unoccupied. Range 0...30°C in
0.5K increments. (FS = 28.0°C)
P-BAND Proportional band, heating and cooling. Range
0.5...99.5K in 0.5K increments. (FS = 5.0K)
I-TIME Reset time. range 0...999 seconds. (FS = 0)
N.B. the range is 999 and not 99.9.
N.B. 0 = P-control, no integration factor.
CAL Temperature reading calibration. The sensor
value can be corrected ±3K in 0.1K increments.
N.B. Use with care. All units are factory calibrated.
Presence detection. ON / OFF. When active, one
of two symbols will be displayed to indicate
which of the two running modes is active.
Man in rectangle = Occupied mode
Man outside rectangle = Unoccupied mode
Setpoint offset
During normal running the configured sepoint value can be
offset ±3K in 0.5K increments.
Klick on either the + button or the - button and the present
displacement will be shown. Change the value using the
+ button or the - button to increase or decrease the value. The
ALD24A1 will automatically revert to normal running display
after 3 seconds of button inactivity.
EMC emission and immunity standard
This product conforms with the requirements of European
EMC standards CENELEC EN50081-1 och EN50082 - 1 and
carries the CE mark.
1
2
3
4
5
6
7
8
Supply 24 V AC
Supply neutral
Output 0...10 V
Signal neutral
Change-over
Signal neutral
External sensor
Presence signal
°C
HEATING
COOLING
SETP.
P-BAND
I-TIME
CAL
Menu
parameter
Running mode
Output
Heating Cooling
Actual temperature
INSTRUCTIONS INSTRUCTIONS
All neutrals internally connected

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Regin ALD24A1 and is the answer not in the manual?

Regin ALD24A1 Specifications

General IconGeneral
BrandRegin
ModelALD24A1
CategoryController
LanguageEnglish

Related product manuals