94
Number of times the fluid level may fall below the level set
until alarm is triggered. Reset to 1 approximately 30 minutes
after the most recent alarm. 0 = Alarm counter off.
Appears only if H2O = yES (→ SEt Fun, Section 7.2).
Relays 1 to 3 are used to acknowledge the following operat-
ing conditions:
“rEG” Relay 1 is active if the control is switched on.
“ALA” Relay 1 functions as alarm relay.
“CLC” Relay 1 is active if the timer is switched on.
Band monitoring is based on the active set value, e.g.
40 (°C)/72 (°F) corresponds to 40 °C/72 °F above or below
the set value.
Programming of any desired temperature “X” at which the
relay is activated.
if in
“SAL” Reset alarm by pressing “Alarm Reset” key.
“oC” Automatic resetting of alarm.
Relay 1 is activated if the unit is on normal operation or on
leak-stop mode.
Relay 1 is activated if the level contact 1 is closed (level
sufficient).
SP
P
P
n.LE
...
0 to 40
P
r1
rEG
SP
ALA
CLC
40
Lln
P
Lln 100
0 to 99 (°C)
0 to 178 (°F)
0 to 420 (°C)
0 to 788 (°F)
H1
H2
FLC
FLo
LEU
PU
S
–
–
S1
–
S1
–
S2
–
S2
–
PPU
if in
run
LE1
SEt
PEr
→ Section 7.7
r1
Std
:
SEt
PEr
→ Section 7.7
r1
ALL
:
r1
P
SAL
SAL/oC