remeha W40/60-m ECO
6.4.10 User settings
The user can set the following parameters to the
required values.
1.Flow temperature (basic setting 80˚C).
- Press the 'mode'-key until the digit 1. (with dot)
appears in the 'code'-display.
- The set value 8 0 is shown in the temperature
display.
- Now set the required flow temperature, using the
'▲'- and '▼'-keys.
Code Description
1. 7 0 Required flow temperature
- Press the 'store'-key to store the new value (value
will blink twice).
- Press the 'mode'-key until the digit without dot
appears in the 'code'-display.
2.Pump switching (basic setting: pump continues to
operate for 5 minutes)
- Press the 'mode'-key until the digit 1. (with dot)
appears in the 'code'-display.
- Press the 'step'-key until the digit 2. appears in the
'code'-display.
- Set the required value, using the '▲'- and '▼'-keys.
3.D.H.W. setting (basic setting 65˚C). Only with sensor.
- Press the 'mode'-key until the digit 1. (with dot)
appears in the 'code'-display.
- Press the 'step'-key until the digit 3. appears in the
'code'-display.
- Set the required value, using the '▲'- and '▼'-keys.
Code Description
2. 0 0 Pump continues to operate for 10 sec.
2. X X Pump continues to operate for
1 - 15 min. (example: X X = 05)
2. 9 9 Continuous pump operation
- Press the 'store'-key to store the new value (value
will blink twice).
- Press the 'mode'-key until the digit without dot
appears in the 'code'-display.
Code Description
3. 6 5 required temperature
- Press the 'store'-key to store the new value (value
will blink twice).
- Press the 'reset'-key to return into the operating
mode.
Operation is as follows:
Imagine: the setpoint for D.H.W. temperature has been
preset at 65°C, the D.H.W. cut-in temperature differen-
tial at 5°C, and the maximum flow temperature during
D.H.W. operation at 80°C (factory settings).
The appliance will modulate at the preset maximum flow
temperature during D.H.W. operation, and will shut down
at a D.H.W. temperature of 70°C (preset value +5°C).
The appliance will cut back in at a D.H.W. temperature
of 65°C (preset D.H.W. temperature
+5°C - D.H.W. cut-in temperature differential).
Both the D.H.W. cut-in differential and the maximum flow
temperature during D.H.W. operation can only be set via
the service menu (para. 10.3.9 and 10.3.10).