Error F5: Condenser fan speed not alright
Shut off the power supply and turn it on 5
seconds later. Is it still displaying the error
code?
The unit operates normally.
Shut off the power sopply, rotate the cross
fan by hand. Does it rotate properly?
Disassembly the connection
between fan and motor,
check if the bearing is
normal?
Check the wires of fan motor. Are all the
connections good?
Correct the
connections.
Replace
indoor fan
motor.
Replace the
bearing.
3
Replace
indoor fan
motor.
4
5
6