2.3 Cooling and heating capacity
Cooling capacity WLT 30 EC - WLT 50 EC
VS LV SD
Medium
nominal
Medium inlet
5 °C 7 °C 9 °C 11 °C 13 °C
Cooling capacity
Medi
um
flow
rate
[m
3
/h]
Pres-
sure
loss
[kPa]
Q
K
[kW]
Q
S
[kW]
Q
K
[kW]
Q
S
[kW]
Q
K
[kW]
Q
S
[kW]
Q
K
[kW]
Q
S
[kW]
Q
K
[kW]
Q
S
[kW]
WLT 30
EC
1 150 18 0.230 13.0 0.95 0.55 0.82 0.50 0.64 0.47 0.49 0.41 0.40 0.35
2 360 33 0.323 13.0 2.17 1.63 1.88 1.27 1.46 1.20 1.12 1.04 0.91 0.88
3 450 39 0.370 15.6 2.49 1.78 2.15 1.46 1.67 1.38 1.28 1.20 1.04 1.01
4 510 43 0.397 17.0 2.67 2.26 2.31 1.60 1.79 1.51 1.37 1.31 1.12 1.11
5 560 45 0.48 23.1 3.25 2.77 2.81 1.95 2.18 1.84 1.67 1.60 1.36 1.35
WLT 40
EC
1 150 19 0.240 13.0 0.95 0.55 0.82 0.50 0.64 0.47 0.50 0.41 0.42 0.36
2 405 34 0.379 13.7 2.54 1.63 2.21 1.48 1.68 1.32 1.36 1.22 1.13 1.06
3 480 38 0.411 15.2 2.75 1.78 2.39 1.61 1.82 1.44 1.47 1.33 1.22 1.15
4 590 42 0.472 19.0 3.69 2.26 3.21 2.05 2.44 1.83 1.97 1.69 1.64 1.47
5 625 45 0.640 31.3 4.17 2.77 3.63 2.51 2.76 2.24 2.23 2.07 1.86 1.80
WLT 50
EC
1 150 18 0.250 19.5 0.98 0.58 0.84 0.51 0.67 0.49 0.55 0.45 0.45 0.38
2 570 32 0.611 19.5 4.15 2.73 3.56 2.42 2.82 2.31 2.34 2.15 1.89 1.80
3 470 40 0.689 23.5 4.68 3.13 4.02 2.78 3.18 2.65 2.65 2.47 2.14 2.07
4 910 46 0.763 27.3 5.17 3.47 4.44 3.08 3.52 2.93 2.92 2.73 2.36 2.29
5 950 47 0.830 31.0 5.59 3.80 4.80 3.37 3.80 3.21 3.16 2.99 2.55 2.51
Air inlet temperature TK 27 °C / FK 19 °C, 0% Glycol concentration, max. air flow
Q
K
= Cooling capacity
, total
Q
S
= Cooling capacity, sensitive
LV = Air flow [m
3
/h]
SD = Sound pressure level [dB(A)]
VS = Fan stage
REMKO WLT EC series
12