- 4 -
E4L E4
H L H L
RC210 90 68 120 68
RC220-RC265 90 110 120 110
RC270-RC280,
RC88
100 160 130 160
RCG90-RCG100 155* 200* 185* 200*
Tabell 14pt bold
Bold på rubriker uppe, allt under ska vara regular.
Allt utom spalten med RC-förteckningar ska vara
centrerat i våg och lodrätt. RC-spalten ska vara
vänsterlagd.
Strl på texten varierar beroende på utrymme men
10pt är standard
www.rotork.com www.remotecontrol.se
Name Spec.
DEAD BAND Mechanical Steps at least 0.2mA
What is DEAD BAND ?
It’s an area/band where no action occurs due to the actuator input.
If the user inputs 12mA (50%), the actuator is supposed to stop exactly at 50% poaition. The actuator repeats from open
to close in order to stop at 50% position at this point.
This is what we call hunting, and if the hunting effect repeatedly occurs the motor can be damage. Therefor a dead band
is set to have some area in order to prevent this from happening.
It’s set to have 0.05mA per gradation. If it is at 1PH when shipped from the factory, it is set to have a 0.2mA dead band. If
it is at 3PH, on the other hand, it is set to have a 0.3mA dead band.
ex) If it is set to have a 0.2mA dead band, the actuator is positioned between 11.8mA to 12.2mA.
In case the actuator stops at the position of 12.1mA, the second least movement area will be at
12.3mA. At this position no action occurs even when there is the input signal.
5
DEAD BAND
6
OTS, CTS Connector
8
OLS, CLS Connector
9
Potentiometer Connector
P3
P1
P2
Color Resistance
P1 White LOW
0 ~ 1000ΩP2 Blue COM
P3 Black HIGH
When shipped from the factory and at full close, it is set at 80 ~ 120Ω.
( *Refer to P13 for Potentiometer setting)