EasyManuals Logo

Resol DeltaSol BS/2 User Manual

Resol DeltaSol BS/2
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
en
11
InstallationIndications, functions and optionsMessages Commissioning Operation and function
5 Commissioning
2 backwards (-)
1 forwards (+)
3 (selection /
confirmation)
Î Connect the device to the mains
The controller runs an initialisation phase in which the operating control LED flash-
es red / green.
When the controller is commissioned or when it is reset, it will run a commission-
ing menu. The commissioning menu leads the user through the most important
adjustment channels needed for operating the system.
adjustment mode flashing
Operation
changing a value flashing
confirming a value not flashing
to the next
parameter
1
1
3
3
2
2
1. Language
Î Adjust the desired menu language.
LANG
Language selection
Selection: dE, En, Fr
Factory setting: dE
2. Temperature unit
Î Adjust the desired unit.
UNIT
Temperature unit
Selection: °F, °C
Factory setting: °C
3. Maximum store temperature
Î Adjust the maximum store temperature.
S MX
Adjustment range: 4 … 95 °C [40 … 200 °F]
Factory setting: 60 °C [140 °F]
Note:
The controller is also equipped with a
non-adjustable emergency shutdown, deacti-
vating the system if the store reaches 95 °C
[200 °F].
Commissioning

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Resol DeltaSol BS/2 and is the answer not in the manual?

Resol DeltaSol BS/2 Specifications

General IconGeneral
BrandResol
ModelDeltaSol BS/2
CategoryTemperature Controller
LanguageEnglish

Related product manuals