Page #27 background imageLoading...
Page #27 background image
D e lt a S o l
®
BS/3
© RESOL 10082_deltasol_bs/3.monus.indd
27 |
5. Troubleshooting
Operating control lamp
Warning symbols
Operating control lamp flashes red. On the display the
symbols and appear.
VBus
®
terminals
power supply
terminals
fuse
load terminalssensor terminals
ground
terminals
In the case of an error, a message is shown on the display
of the controller:
Sensor defect. An error code instead of
a temperature is displayed in the sensor
display channel.
- 88.8888.8
Cable broken.
Check cable.
Short circuit.
Check cable.
Disconnected Pt1000 temperature sen-
sors can be checked with an ohmmeter. In
the following table, the resistance values
with the corresponding temperatures are
shown.
Operating control lamp off.
Check the power supply. Is it disconnected?
no
The fuse of the controller
could be blown. It can be
replaced after the front
cover has been removed
(spare fuse is enclosed in
the accessory bag).
yes
Check the supply line and
reconnect it.
°C °F Ω °C °F Ω
-10 14 961 55 131 1213
-5 23 980 60 140 1232
0 32 1000 65 149 1252
5 41 1019 70 158 1271
10 50 1039 75 167 1290
15 59 1058 80 176 1309
20 68 1078 85 185 1328
25 77 1097 90 194 1347
30 86 1117 95 203 1366
35 95 1136 100 212 1385
40 104 1155 105 221 1404
45 113 1175 110 230 1423
50 122 1194 115 239 1442
Resistance values of the Pt1000-sensors

Other manuals for Resol DeltaSol BS/3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Resol DeltaSol BS/3 and is the answer not in the manual?

Resol DeltaSol BS/3 Specifications

General IconGeneral
BrandResol
ModelDeltaSol BS/3
CategoryController
LanguageEnglish

Related product manuals