3.3.2.1 Bracket Specification
Angle adjustment : Horizontal 180° , Vertical 180°, scale indications 15° each
When you arrange the angle, M4 Set Screw and M10-25 Hexagon Wrench Bolt
has to be released first and tighten again with 24 (N・m) Torgue for Hexagon
Wrench Bolt and 1.5 (N・m) Ttorgue for Set Screw.
Enclosure Material : 316 Stainless Steel
Weight : Body - approximate 2.4㎏, Overall - approximate 3.4㎏
Dimension(Body) : W5.3[134] × H4.6[117] × D4.7[120] (inch[mm])
Dimension(Overall) : W5.3[134] × H6.4[163] × D14.4[366] (inch[mm])
Color : Metal
Wall mounted size : × 4 (5mm bolt)
[Figure 7] Bracket BK-02
3.3.2.2 Installation of detector with bracket to the wall or the ceiling
Necessary tool : Hexagon Wrench Driver, Screw Driver
component : Metric M6-10 × 2 pcs, Metric M5-30 × 4pcs
Flame detector's body and cover has to be combined with M6-35 Hexagon Wrench
Driver at 5(N・m) Torque.
Flame detector and bracket is connected with Hexagon Wrench Bolt at 5(N・m) Torque.