Heat Pump Mode
FIRMWARE: V5.8
Reset button pressed
at any stage
NOTE
The reset button will cancel the 45
minute start delay, reset the Fault 9
counter and clear any stored Fault
Code from the controller memory.
F
B
System Check
Green LED 1 flash
90 minutes has
elapsed?
At least 15 minutes
since the circulator
last ran?
Evaporator sensor
< 1ºC for more than
15 minutes?
YES
Circulator on
Circ. Speed: Maximum
Green LED 4 flashes
NO
Faults 1, 5 or 6
detected?
Circulator has been
on for 30 seconds?
Circulator off
Green LED 1 flash
Circulator off
Green LED Off
YES
NO
L
Fault detected?
Compressor on
Evaporator fan on
Green LED 2 flashes
Compressor off
Evaporator fan off
Green LED Off
D
YES
Green LED Off
After 30 seconds
Circulator on
Circ. Speed: Variable
YES
HX water outlet
sensor > 35ºC for
more than 2 minutes?
Circulator speed
= maximum?
Fault detected?
NO
Compressor has
been operating for at
least 10 minutes?
Evaporator sensor
< -3ºC or > 40ºC?
NO
Circ. Speed: Maximum
Green LED 3 flashes
YES
Compressor off
Evaporator fan off
Circulator off
G
Compressor has
been operating for at
least 10 minutes?
Fault detected?YES
NO
Compressor off
Evaporator fan off
Circulator off
Green LED Off
YES
Compressor off
Evaporator fan off
Circulator off
Green LED Off
YES
Evaporator sensor
< -3ºC or > 40ºC?
NO
Compressor off
Evaporator fan off
Circulator off
Tank
sensor > 60ºC?
12I G
Clear Fault Code from
controller memory
Reset Fault 9 counter
YES
E
NO
NO
J
YES
YES
Compressor off
Evaporator fan off
Circulator off
Green LED Off
YES
Compressor has
been operating for at
least 10 minutes?
NO
HX water outlet
sensor > 22ºC?
NO
NO
NO
YES
NO
YES
H D
NOYES
NO
Fault detected?
D
NO
D
YES
NO
NO
YES
YES
45 minute start delay
has elapsed? (From
last compressor shut
down or from
restoration of power.)
YES
NO
NO
Compressor
sensor > 60ºC?
YES
YES
Fault detected?