TM077: 325 & 410 Series II Heat Pump Service Instructions
Rev 00: Issued April 2014
Component Tests 10 – 13
Using a multimeter set on the AC voltage
scale, measure between the active (blue)
and neutral (black) terminals of the fan
plug at the controller.
Normal voltage is 240V AC.
Unplug the fan from the controller and
using a multimeter set on the resistance
(ohms) scale, measure between the
disconnected fan plug pins. The following
run and start winding results should be
obtained:
Blue & black wires (Run): 650Ω
Blue & brown wires (Start): 375Ω
Unplug the fan from the controller and
using a multimeter set on the capacitance
(µF) scale, measure between the two rear
pins of the jack on the controller.
Normal capacitance is 1.5 micro Farads
(1.5µF).
Using a multimeter set on the AC voltage
scale, measure between the active (brown)
and neutral (blue) terminals of the
circulator plug at the controller.
Normal voltage is 240V AC.