29
Field Conversions
SEE CRITICAL HOSE CLAMP LOCATION NOTE
IN THE GENERAL COVERSION INSTRUCTIONS.
5
CUT
IF REQ’D.
INSTALL
HOSE E
HOSE F
CUT
INSTALL
CUT
INSTALL
ROTATE
UNIT 90°
5a - ROTATE UNIT 90
5b - CUT 1/4" VENT HOSE TO FIT (APPROX. 5-1/2") AND INSTALL AS SHOWN.
5c - CUT HOSE E AT LINE 1- INSTALL
NOTE: MAKE SURE CUT IS STRAIGHT AND SQUARE
5d - CUT HOSE F ON LINE CORRESPONDING TO UNIT WIDTH AND INSTALL
NOTE: 17.5": LINE 1, 21": LINE 2, 24.5": DO NOT CUT
NOTE:
USE SOAPY WATER TO FACILITATE EASY
HOSE AND TUBE ASSEMBLY
1/4” TUBE CUT
TO FIT (APPROX. 4”)
5a
5b
5c 5d
DISCARD
4
HOSE A
DISCARD
INSTALL
4a - REMOVE METAL BRACKET AND THE Ø.403
DRAIN PLUG- DISCARD.
4b - REMOVE HOSE A - DISCARD
4c - INSTALL Ø .559" CONDENSATE DRAIN PLUG
AND CONDENSATE TRAP GASKET AS SHOWN.
4d - INSTALL CONDENSATE TRAP IN JACKET USING
(3) SCREWS.
NOTE:
TO PREVENT DAMAGE TO THE TRAP, THE INSTALLER
MAY ELECT TO INSTALL IT DURING A LATER STEP.
(AFTER THE UNIT IS ROTATED)
4a
4b
4c
4d
RECTANGLE PLUG
DISCARD
DRILL (3)
Ø1/8" HOLES
3a - REMOVE RECTANGLE FLUSH MOUNT PLUG
FROM JACKET SIDE-DISCARD
3b - PRE-DRILL (3) Ø 1/8" HOLES AS SHOWN
FOR CONDENSATE TRAP
3a
3b
3
NOTE: REMAINING STEPS SHOWN WITH FURNACE IN HORIZONTAL RIGHT ORIENTATION