FIGURE 10
CONCENTRIC VENT KIT NO. RXGY-E03A
(DIRECT VENT INSTALLATIONS)
HORIZONTAL INSTALLATION
VERTICAL INSTALLATION
1" MAXIMUM
FIELD-SUPPLIED
STRAP
NOTE: AIR INTAKE NOT
ORIENTATION SENSITIVE.
ITEM No. DESCRIPTION
1 2.5
" PVC PIPE SCHEDULE 40 -- 37.125" LONG
2 4
" PVC PIPE SCHEDULE 40 -- 24" LONG
33
" x 3" x 4" SPECIAL CONCENTRIC FITTING
43
" x 45° STREET ELBOW (FIELD SUPPLIED)
5 PVC RAINCAP
CONCENTRIC TERMINATIONS
CONCENTRIC VENT KIT
NO. RXGY-E03A (SEE FIGURE 10)
This kit is for vertical and horizontal
intake air/vent runs. One
5-in. diameter hole is required for
installation. See Figure 10 for the gen-
eral layout. Complete installation
instructions are included with the kit.
MAINTAIN 12 IN.
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
A
A
A
NOTE: Drain tee is not needed for the inlet pipe.
NOTE:
The following IPEX brand con-
centric terminations (System 636) may
be purchased in the field
and used in
place of factory supplied kits:
3” Concentric Kit Item # 196006
20