26
GENERAL DATA
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capaci-
ty is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certied in accordance with the Unitary Air Conditioner
Equipment certication program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with AHRI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet
bulb at AHRI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
Model RHPDZT Series 102AYG 102AYH 120ACF
120ACG
Cooling Performance1 Continued ->
Gross Cooling Capacity Btu [kW] 100,000 [29.31] 100,000 [29.31] 119,000 [34.87]
119,000 [34.87]
EER/SEER2 11/NA 11/NA 11/NA
11/NA
Nominal CFM/AHRI Rated CFM [L/s] 3400/3350 [1604/1581] 3400/3350 [1604/1581] 4000/4060 [1888/1916]
4000/4060 [1888/1916]
AHRI Net Cooling Capacity Btu [kW] 97,000 [28.43] 97,000 [28.43] 114,000 [33.4]
114,000 [33.4]
Net Sensible Capacity Btu [kW] 71,000 [20.8] 71,000 [20.8] 82,800 [24.26]
82,800 [24.26]
Net Latent Capacity Btu [kW] 26,000 [7.62] 26,000 [7.62] 31,200 [9.14]
31,200 [9.14]
IEER3 14.1 14.1 14.1
14.1
Net System Power kW 8.47 8.47 10.13
10.13
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating 97,000 [28.43] 97,000 [28.43] 112,000 [32.82]
112,000 [32.82]
System Power KW / COP 7.99/3.4 7.99/3.4 9.03/3.4
9.03/3.4
Low Temp. Btuh [kW] Rating 58,000 [17.00] 58,000 [17.00] 68,000 [19.92]
68,000 [19.92]
System Power KW / COP 7.54/2.26 7.54/2.26 8.3/2.26
8.3/2.26
Compressor
No./Type 1/Scroll 1/Scroll 1/Scroll
1/Scroll
Outdoor Sound Rating (dB)5 88 88 88
88
Outdoor Coil - Fin Type Louvered Louvered Louvered
Louvered
Tube Type MicroChannel MicroChannel MicroChannel
MicroChannel
MicroChannel Depth in. [mm] 1.26 [32] 1.26 [32] 1.26 [32]
1.26 [32]
Face Area sq. ft. [sq. m] 22.4 [2.08] 22.4 [2.08] 28.8 [2.68]
28.8 [2.68]
Rows / FPI [FPcm] 1 / 16 [6] 1 / 16 [6] 1 / 16 [6]
1 / 16 [6]
Refrigerant Control TX Valves TX Valves TX Valves
TX Valves
Indoor Coil - Fin Type Louvered Louvered Louvered
Louvered
Tube Type MicroChannel MicroChannel MicroChannel
MicroChannel
MicroChannel Depth in. [mm] 1.26 [32] 1.26 [32] 1.26 [32]
1.26 [32]
Face Area sq. ft. [sq. m] 10.9 [1.01] 10.9 [1.01] 13.2 [1.23]
13.2 [1.23]
Rows / FPI [FPcm] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8]
1 / 20 [8]
Refrigerant Control TX Valves TX Valves TX Valves
TX Valves
Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller
Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1
Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775]
8000 [3775]
No. Motors/HP 2 at 1/2 HP 2 at 1/2 HP 2 at 1/2 HP
2 at 1/2 HP
Motor RPM 1075 1075 1075
1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal
FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
1/15x15 [381x381]
Drive Type Belt (Adjustable) Belt (Adjustable) Belt (Adjustable)
Belt (Adjustable)
No. Speeds Dual Dual Dual
Dual
No. Motors 1 1 1
1
Motor HP 3 3 2
3
Motor RPM 1725 1725 1725
1725
Motor Frame Size 56 56 56
56
Filter - Type Disposable Disposable Disposable
Disposable
Furnished Yes Yes Yes
Yes
(NO.) Size Recommended in. [mm x mm x mm] (4)2x20x20 [51x508x508] (4)2x20x20 [51x508x508] (4)2x25x20 [51x635x508]
(4)2x25x20 [51x635x508]
Refrigerant Charge Oz. [g] 197 [5585] 197 [5585] 214.4 [6078]
214.4 [6078]
Weights
Net Weight lbs. [kg] 821 [372] 822 [373] 863 [391]
873 [396]
Ship Weight lbs. [kg] 860 [390] 861 [391] 902 [409]
912 [414]