29
ELECTRICAL DATA - RHPDZS SERIES
090ACA
090ACB 090ACC 090ACF 090ACG 090ACH 090ADA 090ADB 090ADC
Unit Information
Unit Operating Voltage Range 187-253
187-253 187-253 187-253 187-253 187-253 414-506 414-506 414-506
Volts 208/230
208/230 208/230 208/230 208/230 208/230 460 460 460
Phase 3
3 3 3 3 3 3 3 3
Hz 60
60 60 60 60 60 60 60 60
Minimum Circuit Ampacity 44
46 46 44 46 46 19 20 20
Minimum Overcurrent Protection Device
Size
50
60 60 50 60 60 25 25 25
Maximum Overcurrent Protection Device
Size
60
70 70 60 70 70 25 25 25
Compressor Motor
No. 1
1 1 1 1 1 1 1 1
Volts 200/230
200/230 200/230 200/230 200/230 200/230 460 460 460
Phase 3
3 3 3 3 3 3 3 3
RPM 3450
3450 3450 3450 3450 3450 3450 3450 3450
HP, Compressor 1 7
7 7 7 7 7 7 7 7
Amps (RLA), Comp. 1 25.3
25.3 25.3 25.3 25.3 25.3 9.6 9.6 9.6
Amps (LRA), Comp. 1 184
184 184 184 184 184 84 84 84
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
Condenser Motor
No. 2
2 2 2 2 2 2 2 2
Volts 208/230
208/230 208/230 208/230 208/230 208/230 460 460 460
Phase 1
1 1 1 1 1 1 1 1
HP 1/2
1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Amps (FLA, each) 2.5
2.5 2.5 2.5 2.5 2.5 1.5 1.5 1.5
Amps (LRA, each) 5.6
5.6 5.6 5.6 5.6 5.6 3.1 3.1 3.1
Evaporator Fan
No. 1
1 1 1 1 1 1 1 1
Volts 208/230
208/230 208/230 208/230 208/230 208/230 460 460 460
Phase 3
3 3 3 3 3 3 3 3
HP 2
3 3 2 3 3 2 3 3
Amps (FLA, each) 6.6
9.1 9.1 6.6 9.1 9.1 3.2 4.6 4.6
Amps (LRA, each) 47
74.5 74.5 47 74.5 74.5 24 38.1 38.1
ELECTRICAL DATA