RECYCLING AND DISPOSAL
77
APPENDIX
APPENDIX
Menu
Par.
No.
Nr. dis-
played
Display
Description Range
Default
setting
UM
Access
type
Category
M3 73
Boiler
Address
Denes the way in which the boiler is managed.
Managing,
Stand-alone,
Dependent
Stand-
alone
I Cascade
M3 169
Max.
Setp.
Offset
Down
Denes the maximum decrease in the primary
circuit's cascade set-point and is based on the sec-
ondary circuit's sensor reading.
0 - 72
(0 - 40)
5.6 (2) °F (°C) I Cascade
M3 170
Max.
Setp.
Offset
Up
Denes the maximum increase in the primary
circuit's cascade set-point and is based on the sec-
ondary circuit's sensor reading.
0 - 72
(0 - 40)
9 (5) °F (°C) I Cascade
M3 171
Start
Mod.
Delay
Fact.
Denes the time in minutes from the moment the
request is triggered until the activation of the set-
point increases or decreases provided for by Par. 169
and 170.
0 - 60 40 Min. I Cascade
M4 98
Appli-
ance
Settings
Supports uploading the values of Par. 92, 93 and 94
from a set of pre-dened rpm values that identies
the boiler type.
1 - 26
Array AR
SE 75 P=25
Array AR
SE 117
P=23
I General
M4 97
IO Con-
gura-
tion
Supports uploading the values of Par. from 116
to 128 from a set of pre-dened rpm values that
denes the conguration of the boiler's inputs and
outputs.
10 10 I General