ENGLISH
DEFAULT VALUE
FACTORY SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCES
LEVEL NOTES
SET
VALUE
SETTINGS USER
TIME & DATE USER
LANGUAGE ITALIANO / ENGLISH / ... USER
BACKLIGHT 5 min 1 min 15 min USER
TIME SCHEDULE USER
MAIN
USER
Only IF POR=1
ZONE 1
USER
Only IF POR=1
ZONE 2
USER
Only IF POR=1
DHW USER
DHW HEAT PUMP USER
TECHNICAL INSTALLER
INSTALLATION INSTALLER
ZONES MANAGER INSTALLER
MODIFY ZONE MAIN MAIN / ZONE 1 / ZONE 2 INSTALLER
ACTUATION
TYPE
ITRF05/AKM ITRF05/AKM BE16
INSTALLER
Only MAIN zone
REQUEST TYPE THERMOSTAT
THERMOSTAT / TEMPERAURE
PROBE / REC10 MASTER / REC10
SLAVE
INSTALLER
BE16 ADDRESS -- 1 6
INSTALLER
Only zones with
ACTUATION=BE16
HYDRAULIC
CONF
DIRECT ZONE DIRECT ZONE MIXING ZONE
INSTALLER
Only zones with
ACTUATION=BE16
ZONE TYPE HIGH TEMP HIGH TEMP LOW TEMP INSTALLER
MIN CH SET
40 °C (AT)
20 °C (BT)
20 °C MAX CH SET INSTALLER
MAX CH SET
80,5 °C (AT)
45 °C (BT)
MIN CH SET
80,5 °C (AT)
45 °C (BT)
INSTALLER
CHANGE NAME INSTALLER
PI -
PROPORTIONAL
5099
SERVICE
Only mixing zones with
ACTUATION=BE16
PI - INTEGRAL 10 0 99
SERVICE
Only mixing zones with
ACTUATION=BE16
VALVE RUN 120 sec 0 sec 240 sec
SERVICE
Only mixing zones with
ACTUATION=BE16
CLOSING AT
POWER ON
140 sec 0 sec 240 sec
SERVICE
Only mixing zones with
ACTUATION=BE16
OUTLET OVER 55 °C 0 °C 100 °C
SERVICE
Only BT zones with
ACTUATION =BE16
OUTLET OVER
TEST TIME
0 min 0 min 240 min
SERVICE
Only BT zones with
ACTUATION =BE16
OUTLET OVER
WAIT TIME
2 min Valve run 240 min
SERVICE
Only BT zones with
ACTUATION =BE16
Structure of the MENU tree of the REC10