15
2915858
Installation
5.5.3 Securing the burner to the boiler
Separate the combustion head from the burner body by
loosening the screws 1) and 2) and withdrawing the
group A) from the holding bars 3).
Fix the group B) to the boiler front plate 4) using the
gasket 5) provided as accessory.
5.6 Positioning the probe - electrode
Provide an adequate lifting system.
The seal between burner and boiler must be
airtight.
Do not turn the ionization probe, maintain the
drawing position; should it be close to the ignition
electrode, damage may occur to the control box
amplifier.
The right positions of the ionisation probe and of
the ignition electrode (Fig. 11) is obtainable by co-
inciding their insulators planes with sloping planes
of the fastening support.
Respect the dimensions shown in Fig. 11.
D101
PROBE
ELECTRODE
Fig. 11