EasyManua.ls Logo

Riello GAS Series - Technical Description of the Burner; Technical Data; Electrical Data

Riello GAS Series
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
2915858
GB
Technical description of the burner
4.1 Models available
4.2 Technical data
Tab. A
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1,013 mbar - Altitude 0 m a.s.l.
(2)
Pressure at test point with zero pressure in combustion chamber and at maximum burner output.
(3)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
power is measured with the “Free Field” method, as per EN 15036, and according to an accurate “Accuracy: Category 3” measurement, as de-
scribed in EN ISO 3746.
4.3 Electrical data
Tab. B
4 Technical description of the burner
Designation Voltage Start-up Code
GAS 3 TC 1/240/50 Direct 3751960
GAS 3 TL 1/240/50 Direct 3751961
MODEL GAS 3
Type 519 T55
Output
(1)
kW
Mcal/h
130 - 350
130 - 300
Fuel
NATURAL GAS: G20 - G25 - G31
G20 G25
- Net Calorific Value
kWh/Nm
3
10 8.6
Mcal/Nm
3
8.6 7.4
- Absolute density
kg/Nm
3
0.71 0.78
- Max output
Nm
3/
h
35 43
- Pressure at maximum output
(2)
mbar 11.1 16.4
Operation
- Intermittent (min. 1 stop in 24)
- One-stage
Standard applications Boilers: water, steam, diathermic oil
Ambient temperature °C 0 - 40
Noise levels
(3)
Sound pressure
Sound power
dB(A)
75
85
Combustion air temperature °C max 60
MODEL GAS 3
Type 519 T55
Electrical supply 1N ~ 240V 50 Hz
Motor
rpm
kW
V
A
2750
0.250
240
2
Motor capacitor
µF
V
6.3
450
Ignition transformer
V1 - V2
I1 - I2
230 V - 1x 9 kV
2A - 33 mA
Absorbed electric power kW max 0.4
Protection level IP 40