Start-up, calibration and operation of the burner
6.7 Burner operation
6.7.1 Burner start-up
6.8 Final checks (with burner operating)
Tab. H
Fig. 24
NORMAL
D1799
LOCK-OUT BECAUSE NO IGNITION
Thermostat
Motor
Ignition transformer
Ignition
valve
Ignition flame
Safety + adjust. valve
Operation flame
Lock-out
2 s 40 s 10 s 2 s 40 s 3 s max.
If during operation the flame shuts off, lock-out oc-
curs within 1 sec.
Open the thermostat/pressure switch TL
Open the thermostat/pressure switch TS
The burner must stop
Turn the air pressure switch to the maximum end of scale
position
The burner must stop in lockout
Turn off the burner and cut off the power
Disconnect the minimum gas pressure switch connector
The burner must not start
Obscure the flame sensor
the burner must stop in lockout due to flame loss
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.