11
ENGLISH
EN
MENU
DEFAULT VALUE FACTORY
SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
EXHAUST PROBE RESET INSTALLER
ADD WATER TANK
INSTALLER: only if instantaneous
and “only heating” confi g.
WATER TANK
INSTALLER
REMOVE WATER TANK
INSTALLER
WATER TANK SETPOINT
50°C 37.5°C 60°C
INSTALLER: only if HP enable
to DHW
TANK FROST PROTECT 7°C 0°C 100°C
SERVICE: only if HP enable to
DHW
TANK FR PROT OFFSET 5°C 1°C 20°C
SERVICE: only if HP enable to
DHW
ADD SOLAR PLANT
INSTALLER: only if solar system
is not confi gured
SOLAR INSTALLER
REMOVE SOLAR PLANT INSTALLER
T MAX TANK 60°C 10° 130°C INSTALLER
DELTA T ON PUMP 8°C DELTA T OFF PUMP 30°C INSTALLER
DELTA T OFF PUMP 4°C 4°C DELTA T ON PUMP INSTALLER
INTEGRATION DELAY 0 min 0 min 180 min INSTALLER
COLLECTOR T MIN (- -) (- -)/-30°C - -°C INSTALLER
COLLECTOR T MAX 110°C COLLECTOR T PROT 180°C INSTALLER
COLLECTOR T PROT 110°C 80 °C COLLECTOR T MAX INSTALLER
COLLECTOR T AUTH 40°C COLLECTOR T LOCK 95°C INSTALLER
COLLECTOR T LOCK 35°C -20°C COLLECTOR T AUTH INSTALLER
PWM COLL PUMP 0 min 0 min 30 min INSTALLER
TANK COOLING FUNCTION NOT ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE INSTALLER
SOLAR PUMP MODE OFF OFF / ON / AUTO INSTALLER
ADD HEAT PUMP
INSTALLER: only if HP not
confi gured
HEAT PUMP INSTALLER
ADD HEAT PUMP/REMOVE PDC
INSTALLER: only if HP and boiler
present
USE FREE CONTACTS/USE BUS
USE BUS USE BUS USE FREE CONTACT SERVICE
ENABLE/DISABLE COOLING
FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER
USE FOR DHW/DON’T USE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER: if BE17 present
ANTI FREEZE DELTA SET 1°C 0°C 6°C SERVICE
ENABLE/DISABLE NIGHT REDUCT FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER
REDUCED FREQUENCY 80% 50% 100%
INSTALLER: if NIGHT
REDUCTION active
NIGHT MODE START TIME 20:00 00:00 23:59
INSTALLER: if NIGHT
REDUCTION active
NIGHT MODE STOP TIME 09:00 00:00 23:59
INSTALLER: if NIGHT
REDUCTION active
MIN OUTDOOR TEMP 5°C -5°C 20°C INSTALLER
MIN DHW OUT TEMP
5°C -5°C 20°C
INSTALLER: only if USE FOR
DHW in HP activated
MIN EMERG OUT T -10°C -20°C
10°C and in any case not
over the
MIN OUTDOOR
TEMP value
INSTALLER
BOILER INTEGR DELAY 30 min 1 min 240 min SERVICE
HP INTEGR DELAY 30 min 1 min 240 min SERVICE
BOILER WAITING 2 min 1 min 60 min SERVICE
HEAT PUMP WAITING 2 min 1 min 60 min SERVICE
INTEGRATION OFFSET 5°C 0°C 10°C SERVICE
WINTER SUMMER DELAY 0h 0h 24h SERVICE
WARNING VALIDATION 60 sec 1 sec 300 sec SERVICE
ENABLE CIRC ON/AUTO MODE AUTO ON AUTO
INSTALLER: if boiler in OFF and
AIR PURGING CYCLE not present
DHW HP SETPOINT 60°C WATER TANK SETPOINT 60°C
SERVICE: only if USE FOR DHW
in HP activated
DHW OFFSET
10°C 0°C 25°C
SERVICE: only if boiler with water
tank with probe and USE FOR
DHW in HP activated
ADD PHOTOVOLTAIC
INSTALLER
PHOTOVOLTAIC
INSTALLER
REMOVE PHOTOVOLTAIC INSTALLER
ELECTRIC CONVENIENCE 2 0 +10°C INSTALLER
BACKUP TYPE
1 0 1 INSTALLER
BOOSTER OAT THRESHOLD -7°C MIN EMERG OUT T 15°C INSTALLER