Electrical data and operating times
3.6 Table of times
Tab. A
3.6.1 Operating status indication
Tab. B
Key to layout
Tab. C
Symbol Description Value (sec.)
t0
Standby: the burner is waiting for the heat request, the closure of the gas pressure switch, the open-
ing of the air pressure switch
-
t1 Standby time for an input signal: reaction time, control box remains in waiting mode for t1 2
t1l Flame or flame simulation detected before demand for heat: the control box remains idle. 25
t2 Initialisation standby time: checking time following the main power start-up 4.5
t2l
Checks extraneous light or parasite flame during t2: waiting mode for t2l, then lockout: the motor
does not start
25
t2a
Check whether the air pressure switch has already been moved to the work position before the
required heat: the control box remains in standby status, a lockout follows if the air pressure switch
remains switched for the T2a time.
max 120
t3 Pre-purging time: the fan motor is running, then the gas valve is activated 40
t3l
Checks extraneous light or parasite flame during pre-purging: control box goes into lockout at the
end of t3l
1
t3a
Time for checking the switching of the air pressure switch in the operating position during the pre-
purging time: if the pressure switch does not change over within t3a there is a lockout.
max 15
t3r
A recycle attempt is made if there is an air pressure drop during the pre-purging stage: there is then
a lockout in the event of a second loss of air pressure between the 16th second and the 29th; is a
loss of pressure between the 30th second and the 40th, the control box goes immediately into lockout
mode.
-
ts Safety time 3
t4i Total spark ignition time 3
t4a
Air pressure drop checking time during the ts time and the normal operation:
the control box locks out immediately.
1
t4l Reaction time to achieve safety deactivation due to flame loss 1
t5
Delay time between the 1st and 2nd stage: opening time of 2nd stage valve after opening of 1st
stage, depends on the opening time of the air damper servomotor
5 - 25
- Minimum time to reset the control box using reset button 0.4
Minimum time to reset the control box using remote reset 0.8
tr
Re-cycles: max. 3 repeats of the complete start-up sequence in the case of flame loss during opera-
tion; the final action at the last attempt following flame failure is a lockout
3
re-cycles
Status
Reset button
colour
Seconds Colour code
Awaiting a heat request, awaiting the closure of the gas
pressure switch, awaiting the opening of the air pressure
switch
- - - -
Awaiting heat request with continuous purging
ORANGE
Blink
0.5 2.5
Pre-purging, or awaiting air pressure switch closure, or
long pre-purging
ORANGE
Blink
0.5 0.5
Safety time without flame
GREEN
Blink
0.5 0.5
Safety time with flame GREEN - -
Normal operating position GREEN - -
ON OFF Colour code
RED
ORANGE
GREEN