20166443 (1) - 07/2019
Installation, use and maintenance instructions
Light oil burners
Progressive two-stage or modulating operation
CODE MODEL TYPE
20166463 RL 70/M 669 T1
20166476 RL 70/M 669 T1
20166481 RL 100/M 670 T1
20166484 RL 100/M 670 T1
20166486 RL 130/M 671 T1
20166487 RL 130/M 671 T1
GB

Questions and Answers

  • E
    Erica BlackburnSep 10, 2025
    Why won't my Riello RL 70/M go to 2nd stage?
    • N
      nburtonSep 10, 2025
      If the Riello Burner does not pass to the 2nd stage, it could be because control device TR does not close, so adjust or replace it. It could also be due to a defective control box, so replace it.
  • B
    Brian GriffinSep 12, 2025
    Why does Riello RL 70/M Burner pump lose prime?
    • Y
      ywhitneySep 12, 2025
      If the pump loses prime after a prolonged pause in your Riello Burner, it could be because the return pipe is not immersed in fuel, so bring it to the same height as the suction pipe. Alternatively, air might be entering the suction piping, so tighten the connectors.
  • T
    Thomas McclainSep 14, 2025
    What causes a Riello Burner to stop and lock out during operation?
    • C
      Charles WhiteSep 14, 2025
      If the burner stops in lock out during operation, it may be due to a dirty or defective photocell, so clean or replace it.
  • A
    Angelica Miller MDSep 15, 2025
    Why is my Riello Burner pump leaking oil?
    • K
      Krystal ReedSep 15, 2025
      If the pump leaks light oil in your Riello Burner, it's likely due to leakage from the sealing organ, so replace the pump.
  • M
    Melanie LynchSep 18, 2025
    What causes an internally rusted pump in Riello RL 70/M Burner?
    • C
      Christine LarsenSep 18, 2025
      If the pump is internally rusted, it may be due to water in the tank, so remove the water from the tank bottom with a separate pump.
  • M
    melissa87Nov 24, 2025
    What to do if Riello RL 70/M Burner locks out after pre-purge?
    • T
      thompsonsuzanneNov 25, 2025
      If your Riello Burner locks out after pre-purge and the safety time, and no flame appears, consider these potential causes: There might be no fuel in the tank, or water at the tank bottom, so top up the fuel level or remove the water. The head and air damper adjustments might be inappropriate, requiring adjustment. The light oil solenoid valves could be failing to open, so check connections and replace the coil if necessary. The nozzle might be clogged, dirty, or deformed, so replace it. The firing electrodes might be dirty or poorly adjusted, so adjust or clean them. The electrode could be grounded due to broken insulation, so replace it. The high voltage cable could be defective or grounded, or deformed by high temperature, so replace it and protect it. The ignition transformer could be ...

Riello RL 70/M Specifications

General IconGeneral
Burner TypeMonoblock
Fuel TypeLight Oil
Motor Power0.75 kW
Air RegulationMechanical
Protection DegreeIP 40
Electrical Supply230V, 50Hz