16
Verification of the SECURIPACK
:
The correct functioning of the safety mechanism must be checked for hose
rupture (incorporated in the SECURIPACK) at least every 500 hours or every
three months. This is to be performed as follows:
•
Go outside, a long way from any flame
source, sparks and any objects that ignite.
•
Apply pressure to the appliance. With the
spanner supplied, loosen the connecting nut
of the hose and unscrew completely: the gas
supply will now be cut off automatically.
Verification of the RIPACK 2200:
DAYLY before starting to work:
1 Check the condition of the hose along its whole length and at the fittings.
We recommend that you replace the hose in the following cases:
•
When a visual inspection has revealed damage (cuts), even if the
damage is superficial.
•
Every 3 years if used intensively.
•
At the latest 5 years after first use.
Note: The date on the hose is the manufacture date.
Only use a replacement hose supplied by RIPACK with its original fittings!
2 Check as follows that the dead man's safety mechanism works correctly:
When you are not working, follow the procedure described in steps 8 and 9 of
the chapter "Operation/igniting the RIPACK 2200" and release the trigger
immediately. The nozzle will go out immediately.
If any of the parts you checked show flaws, please contact your RIPACK dealer.
MAINTENANCE