Installation and Programming Manual
3-30
ZONES: CROSS ZONES
Quick Key Item Default Explanation
2 7
CROSS ZONES
Not for UL Installations
no
cross
zoning
for additional immunity to false alarms, two related
zones may be linked together so that both must be
violated within a designated time interval (between 1
and 9 minutes) before an alarm will result
such linking may be appropriate for use with motion
detectors in “hostile” or “false-alarm prone”
environments
the Pro-24 allows for 10 unique sets (pairs) of zone
links (pairs of zones) which can be manually-
specified, as required
a) from this display, press [ENTER] to reveal the first
zone link
b) from this display, press [ENTER] to modify the first
set (01) of zone links
c) as required, manually select the zone pairs by making
changes to the number of the first zone in the set,
followed by the number of the second zone
if necessary, use the UP-arrow (STAT) and/or
DOWN-arrow (BYP) keys to properly position the
cursor
zones “crossed with themselves” are not valid pairs
you may wish to establish a number of zone links,
but leave them deactivated at this time (see below)
d) press [ENTER] when completed, and select the
parameter governing the pairing, below:
Cross
Zoning
Pair Parameter:
chooses how the Pro-24 will process violations of
paired zones
2 7 1 None
use to temporarily disable any associated
zone pairings
2 7 2 Ordered
use to effect an alarm if it’s desired that the first listed
zone be tripped before the second
2 7
3 Not Ordered
use to effect an alarm in which either zone in the pair
may be tripped first
if so, the specified zone order (1
st
, 2
nd
) has no bearing
on the alarm activation
Time Slot: 1 min
choose a time interval between 1 and 9 minutes
defining the active internal
repeat the entire process, as required, for any additional zone links (up to 10) desired
INSTALLER PROG:
2)ZONES
SUBJECT: ZONES
7)CROSS ZONES ¤
ZONE CROSSING:
01) 01 WITH 01 ¤
CROSSING SET 01:
1ST=01 2ND=01