EasyManua.ls Logo

Rishabh Instruments RISH Master 3430i - Page 42

Rishabh Instruments RISH Master 3430i
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Explanation for 4 X register :
Address Parameter Description
40005
40007
System Voltage
This address is read only and displays System Voltage
40009
System Current
This address is read only and displays System Current
This address is used to set the System type.
Write one of the following value to this address.
1 = 1 Phase 2 Wire (Read only for 1P2W)
2 = 3 Phase 3 Wire 3 = 3 Phase 4 Wire.
Writing any other value will return error .
40011
System Type
40013
Pulse Width
of Relay
This address is used to set pulse width of the Pulse output.
Write one of the following values to this address:
60 : 60 ms
100 : 100 ms
200 : 200 ms
Writing any other value will return error .
40015
Reset
Parameters
Write one of the following values to this address:
0 : Energy Reset 2 : Min Reset
3 : Max Reset 6 : Reset All
Energy display
on Modbus
This address is used to set energy display on MODBUS in Wh,
KWh & Mwh. Write one of the following value to this address.
1 = Energy in Wh. 2 = Energy in KWh.
3 = Energy in MWh.
40021
Node
Address
This register address is used to set Device address
between 1 to 247 .