4. PROTOCOL
IMAE02-E3
29
Continued from the previous page.
(Attribute RO: Read only, R/W: Read and Write)
Name
Iden-
tifier
Data range
Factory set
value
Attribute
Alarm 3 differential gap
setting
1
HC R/W
Alarm 4 differential gap
setting
2
HD
PV bias PB Temperature input:
-1999 to +9999 °C [°F] or
-199.9 to +999.9 °C [°F]
Voltage/current inputs:
-span to +span
However,
within -1999 to +9999
Temperature
input:
0 or 0.0
Voltage/
current
inputs: 0.0
R/W
Analog output scale high
3
HV ALS (Analog output scale low)
to SLH (Setting limiter high limit)
SLH R/W
Analog output scale low
3
HW SLL (Setting limiter [low limit)
to AHS (Analog output scale
high)
SLL R/W
Set data lock function
4
LK 0: Can be changed
1: Can not be changed
0R/W
1
This is an identifier which enables communication at alarm 3 is provided.
2
This is an identifier which enables communication at alarm 4 is provided.
3
This is an identifier which enables communication at analog output is provided.
4
The set data lock function is effective only for the setting performed by key operation. Setting items in the
data lock state cannot be set by key operation, but can a always be selected via communication.
Temperature input:
0 to 100 °C [°F] or
0.0 to 100.0 °C [°F]
Voltage/current inputs:
0.0 to 10.0 % of span.
Temperature
input:
2 or 2.0
Voltage/
current
inputs: