3. SETTING FOR COMUNICATION
IMAE02-E3
11
3.5 Data bit Configuration Setting
Set the data bit configuration during communication. Press the UP or DOWN key to change the numeral.
Symbol Name Setting range Description
Factory
set value
Data bit
configuration
0 to 5
See Data bit
configuration table
Selects data bit configuration
during communication.
0
bIT
Data bit configuration table
Setting Data bit [bit] Parity bit Stop bit [bit]
0 8 None 1
1 8 None 2
27 Even 1
37 Even 2
47 Odd 1
57 Odd 2
Set the same data bit configuration to both the AE500 and connecting host computer.
When the communication parameter was changed, always turn on the power again.
Otherwise, no communication is performed by using the changed value.
If key operation is not performed for more than 1 minute without pressing the SET key after
the device address is set, the AE500 is automatically changed to PV display. In this case, the
set data bit construction returns to the value before the setting is changed.