5. INPUT RANGE TABLES
IMAE02-E3
31
Continued from the previous page.
Input type Input range Code
Input Range
400 to 1800 °C
B01
B
0 to 1820 °C
1
B02
800 to 3200 °F
BA1
0 to 3308 °F
1
BA2
0 to 800 °C
E01
E
0 to 1000 °C
E02
0 to 1600 °F
EA1
0 to 1832 °F
EA2
0 to 1200 °C
N01
N
0 to 1300 °C
N02
0 to 2300 °F
NA1
0 to 2372 °F
NA2
-199.9 to +400.0 °C
2
T01
-199.9 to +100.0 °C
2
T02
-100.0 to +200.0 °C
T03
0.0 to 350.0 °C
T04
T
-199.9 to +752.0 °F
2
TA1
Thermocouple
-100.0 to +200.0 °F
TA2
-100.0 to +400.0 °F
TA3
0.0 to 450.0 °F
TA4
0.0 to 752.0 °F
TA5
0 to 2000 °C
W01
W5Re/W26Re
0 to 2320 °C
W02
0 to 4000 °F
WA1
0 to 1300 °C
A01
0 to 1390 °C
A02
PL II
0 to 1200 °C
A03
0 to 2400 °F
AA1
0 to 2534 °F
AA2
-199.9 to +600.0 °C
2
U01
-199.9 to +100.0 °C
2
U02
U
0.0 to 400.0 °C
U03
-199.9 to +999.9 °F
2
UA1
-100.0 to +200.0 °F
UA2
0.0 to 999.9 °F
UA3
1
Accuracy is not guaranteed between 0 to 399 °C (0 to 799 °F)
2
Accuracy is not guaranteed between
-
199.9 to -100.0 °C (
-
199.9 to -158.0 °F)
Continued on the next page.