15
INSTALLER SETUP MENU
Feature Feature Description Display Adjustment Options
Factorydef
ault
settings
Compressor
Short Cycle
Delay
Cooling
Differential
Heating
Differential
The compressor short cycle
delay setting will not allow the
compressor to be turned on
for 5 minutes after it was last
turned off in order to protect
the compressor.
Next Step
Com Delay
Prev Step
Done
The cooling differential is factory
preset at 0.5°. This means that
whenever the room temperature
heats by 0.5° full degree from
the temperature setting, the
cooling system will turn on.
If the cooling system turns
on too often, increase the
temperature differential.
Next Step
Cool Swing
Prev Step
Done
The heating differential is factory
preset at 0.4°. This means that
whenever the room temperature
cools by 0.4° from the temperature
setting, the heating system will
turn on. If the heating system
turns on too often, increase the
temperature differential.
Next
Step
Heat
Swing
Prev Step
Done
The compressor short cycle
delay setting can be removed
by selecting OFF.
The cooling differential setting
is adjustable from 0.2°F to 2°F.
The heating differential setting
is adjustable from 0.2°F to 2°F.