292 Rockwell Automation Publication 1766-UM001O-EN-P - September 2021
Appendix G          Connect to Networks via Ethernet Interface
Disable the Ethernet Channel Disable the Ethernet channel by performing the following  steps:
1.  From the status file, set the status bit S:36/0 from 0 to 1.
2. Download the project to the MicroLogix 1400 controller.
3. Perform a power cycle in order for the changes to take effect.
IMPORTANT You can only change the status bit S:36/0 in an offline project.
IMPORTANT Consider the following when you enable or disable the Ethernet channel 
using the status bit S:36/0:
• To enable or disable the Ethernet channel, a power cycle on the controller is 
required for the change of status to take effect.
• If the Ethernet channel is set to disable, the other Ethernet-related protocols 
must also be set to disable (except for BOOTP as it returns to enable mode 
even if you set it to disable), in order for the user project to download 
successfully.
• If the Ethernet channel is in disable mode (after a power cycle), you cannot 
set the Ethernet channel and the other Ethernet-related protocols (except 
for BOOTP) back to enable mode at the same time. To do this, you need to 
set the Ethernet channel to enable and perform a power cycle on the 
controller first before you can enable the other Ethernet-related protocols.
• If the Ethernet channel is disabled and you configured the MSG instruction 
for channel 1, the instruction indicates an error as the channel is shut down 
during RUN mode.
IMPORTANT At least 1 of the 3 channels must be active to enable communication with 
the RSLogix 500 software. You cannot disable the Ethernet channel if both 
serial channels are already configured as disabled. If you attempt to 
change the status bit S:36/0 from 0 to 1, it reverts to enable (0) after the 
power cycle.
See also Appendix F
 for information on how to disable the Incoming 
EtherNet/IP Connections.