Rockwell Automation Publication 1734-IN032F-EN-P - September 2022 13
POINT I/O 4 Channel High Density Current Input Module Installation Instructions
Environmental Specifications
Attribute Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 °C Ta +55 °C (-4 °F Ta + 131 °F)
Temperature,
surrounding air, max
55 °C (131 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…+85 °C (-40…+185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration
IEC 60068-2-6, (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…6000 MHz
EFT/B immunity
IEC 61000-4-4:
±3 kV at 5 kHz on power ports
±3 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on shielded ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM @ 150 kHz…80 MHz
Certifications
Certification (when product is marked)
(1)
Value
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
UK and CE
UK Statutory Instrument 2016 No. 1091 and European Union 2014/30/EU EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A and B)
UK Statutory Instrument 2012 No. 3032 and European Union 2011/65/EU RoHS, compliant with:
EN IEC 63000; Technical documentation
Ex
UK Statutory Instrument 2016 No. 1107 and European Union 2014/34/EU ATEX Directive, compliant with:
EN IEC 60079-0; General Requirements
EN IEC 60079-7; Explosive Atmospheres, Protection "e"
II 3 G Ex ec IIC T4 Gc
DEMKO 04 ATEX 0330347X
UL22UKEX2478X
IECEx
IECEx System, compliant with:
IEC 60079-0; General Requirements
IEC 60079-7; Explosive Atmospheres, Protection "e"
II 3 G Ex ec IIC T4 Gc
IECEx UL 20.0072X
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
RCM
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions