3-8 Programming and Parameters
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Display Group (continued)
d024 [Drive Temp]
Present operating temperature of the drive power section.
Values Default: Read Only
Min/Max: 0/120 degC
Display: 1 degC
d025 [Counter Status]
The current value of the counter when counter is enabled.
Values Default: Read only
Min/Max: 0/9999
Display: 1
d026 [Timer Status]
32 bit parameter.
The current value of the timer when timer is enabled.
Values Default: Read Only
Min/Max: 0.0/9999 Secs
Display: 0.1 Secs
32
d028 [Stp Logic Status]
When P038 [Speed Reference] is set to 6 “Stp Logic”, this parameter will display the current step of
the StepLogic profile as defined by parameters A140
-A147 [Stp Logic x].
Values Default: Read Only
Min/Max: 0/7
Display: 1
d029 [Torque Current]
The current value of the motor torque current.
Values Default: Read Only
Min/Max: 0.00/(Drive Rated Amps × 2)
Display: 0.01 Amps
22B-UM001.book Page 8 Tuesday, May 30, 2017 5:22 PM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen Bradley PowerFlex40 and is the answer not in the manual?

Rockwell Automation Allen Bradley PowerFlex40 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen Bradley PowerFlex40
CategoryDC Drives
LanguageEnglish

Related product manuals