3-12 Programming and Parameters
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Basic Program Group (continued)
P038 [Speed Reference] Related Parameter(s): d001, d002, d012, d020, d021, P039, P040,
A051
-A054, A069, A070-A077, A110-A113, A123, A132, A140-A147, A150-A157
Sets the source of the speed reference to the drive.
The drive speed command can be obtained from a number of different sources. The source is
normally determined by P038
[Speed Reference]. However, when A051 - A054 [Digital Inx Sel] is set
to option 2, 4, 5, 6, 11, 12, 13, 14, 15 and the digital input is active, or if A132
[PID Ref Sel] is not set
to option 0, the speed reference commanded by P038
[Speed Reference] will be overridden. Refer to
the flowchart on page 1-23
for more information on speed reference control priority.
Options 0 “Drive Pot” (Default) Frequency command from the potentiometer on the integral
keypad.
Important: This option is not available with IP66, NEMA/UL
Type 4X rated drives. Internal frequency command comes
from A069
[Internal Freq].
1 “InternalFreq”
(IP66, NEMA/UL Type
4X Default)
Internal frequency command from A069
[Internal Freq]. Must
be set when using MOP function.
2 “0-10V Input” External frequency command from the 0-10V or ±10V analog
input or remote potentiometer.
3 “4-20mA Input” External frequency command from the 4-20mA analog input.
4 “Preset Freq” External frequency command as defined by A070
- A077
[Preset Freq x] when A051
- A054 [Digital Inx Sel] are
programmed as “Preset Frequencies” and the digital inputs
are active.
5 “Comm Port” External frequency command from the communications port.
Refer to Appendix C for details.
6 “Stp Logic External frequency command as defined by A070
- A077
[Preset Freq x] and A140
- A147 [Stp Logic x].
7 “Anlg In Mult” External frequency command as defined by the product of the
analog inputs (shown in d020
[Analog In 0-10V] and d021
[Analog In 4-20mA]).
[Analog In 0-10V] × [Analog In 4-20mA] = Speed Command
Example: 100% × 50% = 50%
P039 [Accel Time 1] Related Parameter(s): P038, P040, A051-A054,
A067
, A070-A077, A140-A147
Sets the rate of acceleration for all speed increases.
Values Default: 10.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A067
[Accel Time x]
P040 or A068
[Decel Time x]
0
Acceleration
Deceleration
22B-UM001.book Page 12 Tuesday, May 30, 2017 5:22 PM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen Bradley PowerFlex40 and is the answer not in the manual?

Rockwell Automation Allen Bradley PowerFlex40 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen Bradley PowerFlex40
CategoryDC Drives
LanguageEnglish

Related product manuals