Programming and Parameters 3-23
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Advanced Program Group (continued)
A070 [Preset Freq 0]
(1)
A071 [Preset Freq 1]
A072 [Preset Freq 2]
A073 [Preset Freq 3]
A074 [Preset Freq 4]
A075 [Preset Freq 5]
A076 [Preset Freq 6]
A077 [Preset Freq 7]
Related Parameter(s): P038, P039, P040, A051-A053,
A067
, A068, A140-A147, A150-A157
Values A070 Default:
(1)
A071 Default:
A072 Default:
A073 Default:
A074 Default:
A075 Default:
A076 Default:
A077 Default:
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz
Min/Max: 0.0/400.0 Hz
Display: 0.1 Hz
Provides a fixed frequency command value when A051
- A053 [Digital Inx Sel] is set to 4 “Preset
Frequencies”.
An active preset input will override speed command as shown in the flowchart on page 1-23
.
(1)
To activate A070 [Preset Freq 0] set P038 [Speed Reference] to option 4 “Preset Freq 0-3”.
Input State
of Digital In 1
(I/O Terminal 05
when A051 = 4)
Input State
of Digital In 2
(I/O Terminal 06
when A052 = 4)
Input State
of Digital In 3
(I/O Terminal 07
when A053 = 4) Frequency Source Accel / Decel Parameter Used
(2)
0 0 0 A070 [Preset Freq 0] [Accel Time 1] / [Decel Time 1]
1 0 0 A071 [Preset Freq 1] [Accel Time 1] / [Decel Time 1]
0 1 0 A072 [Preset Freq 2] [Accel Time 2] / [Decel Time 2]
1 1 0 A073 [Preset Freq 3] [Accel Time 2] / [Decel Time 2]
0 0 1 A074 [Preset Freq 4] [Accel Time 1] / [Decel Time 1]
1 0 1 A075 [Preset Freq 5] [Accel Time 1] / [Decel Time 1]
0 1 1 A076 [Preset Freq 6] [Accel Time 2] / [Decel Time 2]
1 1 1 A077 [Preset Freq 7] [Accel Time 2] / [Decel Time 2]
(2)
When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this
table.
A078 [Jog Frequency]
Related Parameter(s): P035, A051-A054, A079
Sets the output frequency when a jog command is issued.
Values Default: 10.0 Hz
Min/Max: 0.0/[Maximum Freq]
Display: 0.1 Hz
22B-UM001.book Page 23 Tuesday, May 30, 2017 5:22 PM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen Bradley PowerFlex40 and is the answer not in the manual?

Rockwell Automation Allen Bradley PowerFlex40 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen Bradley PowerFlex40
CategoryDC Drives
LanguageEnglish

Related product manuals