Programming and Parameters 3-39
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Advanced Program Group (continued)
A135 [PID Integ Time]
Sets the value for the PID integral component when the PID mode is enabled by A132 [PID Ref Sel].
Values Default: 0.1 Secs
Min/Max: 0.0/999.9 Secs
Display: 0.1 Secs
A136 [PID Diff Rate]
Sets the value for the PID differential component when the PID mode is enabled by A132 [PID Ref
Sel].
Values Default: 0.01 (1/Secs)
Min/Max: 0.00/99.99 (1/Secs)
Display: 0.01 (1/Secs)
A137 [PID Setpoint]
Provides an internal fixed value for process setpoint when the PID mode is enabled by A132 [PID Ref
Sel].
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
A138 [PID Deadband]
Sets the lower limit of the PID output.
Values Default: 0.0%
Min/Max: 0.0/10.0%
Display: 0.1%
A139 [PID Preload]
Sets the value used to preload the integral component on start or enable.
Values Default: 0.0 Hz
Min/Max: 0.0/400.0 Hz
Display: 0.1 Hz
22B-UM001.book Page 39 Tuesday, May 30, 2017 5:22 PM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen Bradley PowerFlex40 and is the answer not in the manual?

Rockwell Automation Allen Bradley PowerFlex40 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen Bradley PowerFlex40
CategoryDC Drives
LanguageEnglish

Related product manuals