6 SMC™ Flex Quick Start
Power Wiring
Refer to the product nameplate or the SMC Flex User Manual for device specific information.
Control Terminals
SMC Rating
[A]
Lug Kit
Cat. No.
Wire Strip
Length
Conductor
Range
Max. No. Lugs/Pole Tightening Torque
Line Side Load Side Wire - Lug Lug - Busbar
5…85 — 18…20 mm
2.5…85 mm
2
(#14…3/0 AWG)
——
11.3 N•m
(100 lb•in)
—
108…135 199-LF1 18…20 mm
16…120 mm
2
(#6…250 MCM)
11
31 N•m
(275 lb•in)
23 N•m
(200 lb•in)
201…251 199-LF1 18…20 mm
16…120 mm
2
(#6…250 MCM)
22
31 N•m
(275 lb•in)
23 N•m
(200 lb•in)
317…480 199-LG1 18…25 mm
25…240 mm
2
(#4…500 MCM)
22
42 N•m
(375 lb•in)
28 N•m
(250 lb•in)
625…780 100-DL630 32 mm/64 mm
70…240 mm
2
(2/0…500 MCM)
22
45 N•m
(400 lb•in)
68 N•m
(600 lb•in)
970 100-DL860 26 mm/48 mm
120…240 mm
2
(4/0…500 MCM)
11
45 N•m
(400 lb•in)
68 N•m
(600 lb•in)
1250
100-DL630 32 mm/64 mm
70…240 mm
2
(2/0…500 MCM)
11
45 N•m
(400 lb•in)
68 N•m
(600 lb•in)
100-DL860 26 mm/48 mm
120…240 mm
2
(4/0…500 MCM)
11
Terminal Description Terminal Description Footnotes
11
➂➃ Control Power Input (+) 23➀ PTC Input
➀ Do not connect any additional loads to these
terminals. These “parasitic” loads may cause
incorrect operation.
➁ When set for External Bypass mode, the SMC
Flex can be used to control a properly sized
external contactor and overload once the motor
reaches full speed. The SMC-Flex overload
functionality is disabled in this mode.
➂ RC Snubbers are required on inductive type
loads connected to auxiliary contacts.
➃ Control power on units rated 625…1250 A is
pre-wired internally, from terminal block CP1.
12➂➃ Control Power Common 24➀ PTC Input
13
➀ Controller Enable Input 25 Tachometer Input
14 Ground 26 Tachometer Input
15
➀➂ Option Input #2 27➀ Ground Fault Transformer Input
16
➀➂ Option Input #1 28➀ Ground Fault Transformer Input
17
➀➂ Start Input 29➁➂ Aux Contact #2
18
➀➂ Stop Input 30➁➂ Aux Contact #2
19
➁➂ Aux Contact #1 31➁➂ Aux Contact #3
20
➁➂ Aux Contact #1 32➁➂ Aux Contact #3
21 Not Used 33
➁➂ Aux Contact #4
22 Not Used 34
➁➂ Aux Contact #4