4. Power Pack Specifications Trusted Power System
16 Issue 11 Rockwell Automation Publication PD-T823X
4.4. Efficiency and Power Factor vs. Input Voltage at Full Load
Input voltage
Efficiency (Typical) Power Factor (Typical)
90 Vac 78 % 0.99
100 Vac 79 % 0.99
110 Vac 80 % 0.99
120 Vac 81 % 0.98
180 Vac 82 % 0.98
220 Vac 83 % 0.98
240 Vac 83 % 0.98
264 Vac 84 % 0.98
Table 4 Efficiency and Power Factor vs. Input Voltage at Full Load
When using this table to calculate cable feed requirements, allow, at a minimum, an extra
3 % for variations between units. Actual measured results will depend upon the harmonic
content of the input voltage waveform.
4.5. Output Specification
Parameter Min Type
Max Unit Note
V
OUT
Set Point:
T8231 24 Vdc
T8232 28 Vdc
Regulation (line, load,
temperature and set point)
-2 2 % Measured at remote sense
Remote-sense Drop 0.5 Vdc
I
OUT
(rated):
T8231 (24 V
OUT
) 0 31.25 Adc 750 W maximum
T8232 (28 V
OUT
) 0 26.78
Ripple (20 MHz bandwidth) 150 mVp-p