MC16 Operating Manual 09.01.2020
40/52
(Prealarm) ON
specified by the parameter Upper Limit (Prealarm).
248
Occupancy Lower Limit
(Prealarm) ON
Event
Access Zone
Triggered when the number of users in Access Zones reaches value
specified by the parameter Lower Limit (Prealarm).
249
Occupancy Upper Limit
(Prealarm) Status
Status
Access Zone
Triggered as long as the number of users in Access Zone reaches or
exceeds value specified by the parameter Upper Limit (Prealarm).
250
Occupancy Lower Limit
(Prealarm) Status
Status
Access Zone
Triggered as long as the number of users in Access Zone reaches or falls
below value specified by the parameter Lower Limit (Prealarm).
251
Delayed Occupancy Lower Limit
ON
Event
Access Zone
Triggered with a delay when the number of users in Access Zones is lower by
one than the parameter Lower Limit and higher than zero. The function is not
triggered when zone is empty. Delay in range of 0-254s (by default 30s) is
specified with the parameter OLD= in OPTIONS.CFG text file on controller
memory card.
252
Delayed Occupancy Lower Limit
Status
Status
Access Zone
Triggered with a delay as long as the number of users in Access Zones is
lower by one than the parameter Lower Limit and higher than zero. The
function is not triggered when zone is empty. Delay in range of 0-254s (by
default 30s) is specified with the parameter OLD= in OPTIONS.CFG text file
on controller memory card.
253
Failed Attempts Limit
Event
Access Point
Triggered when failed attempt limit for user identification is reached. The limit
is configured within Access Point configuration.
254
Access Point Disabled
Event
Access Point
Triggered when Access Point is disabled by input functions [257], [259] or as
result of reaching failed attempt limit for user identification.
255
Access Point Enabled
Event
Access Point
Triggered when Access Point is enabled by input functions [258], [259] or
when Failed Attempts Blocking Time elapses.
256
Access Point Disabled Status
Status
Access Point
Triggered as long as Access Point is disabled by input functions [257], [259]
or as result of reaching failed attempt limit for user identification.