Remove connections to CLK and DTA terminals/wires
Connect CLK with DTA
Restart the controller (place and remove jumper on RST contacts see fig. 7 or switch power
supply off/on) LED OPEN (green) shall start to pulsate
Disconnect CLK and DTA
Enter new MASTER PIN (3 to 6 digits) followed with the [#] key or skip this step and press only
the [#] key
Read any card at the reader, this will be a new MASTER card or skip this step and press only
the [#] key
Enter two digits (in range of 00 to 99) by means of keypad, this will be new ID address or skip
this step and press only the [#] key so the default ID=00 could be assigned
After a few seconds the controller shall restart automatically and switch to normal mode
4.2.3 Full Memory Reset procedure (controller without keypad)
Full Memory Reset restores default settings and enables programming of new MASTER card and
controller ID address using card readings.
Remove connections to CLK and IN3 terminals/wires
Connect CLK with IN3
Restart the controller (place and remove jumper on RST contacts see fig. 7 or switch power
supply off/on) the controller shall switch all LED indicators on and shall generate continuous
acoustic signal
Disconnect CLK and IN3 the controller shall switch all LED indicators off and then LED OPEN
and LED STATUS indicators shall pulsate till the end of reset procedure
Read any card at the controller, this will be the new MASTER card. Then the controller shall
generate two short acoustic signals
Read MASTER card X times where X corresponds to the first digit of the required controller ID
address. Each card reading shall temporarily switch LED SYSTEM on. Then wait until the
controller generates two short acoustic signals
Read MASTER card Y times where Y corresponds to the second digit of the required controller
ID address. Each card reading shall temporarily switch LED SYSTEM on. Then wait until the
controller generates three short acoustic signals
After a few seconds the controller shall restart automatically and switch to normal mode
After Memory Reset controller resumes its work with default factory settings and configured
address. You can then test its operation using MASTER card or PIN (if available). Using the MASTER
card/PIN once activates the REL1 output for 4 seconds (LED OPEN ). Using the MASTER card/PIN
twice switches the IO1 output to the opposite state and switches Arm/Disarm Mode (LED STATUS
changes its colour).
4.3 Controller programming
Controllers can be configured by means of:
PR Master software installed on computer connected to the controller via communication
interface (e.g. UT-2USB, UT-4DR) or via CPR32-NET network controller
Commands entered with keypad (limited settings only)
More information on controllers programming can be found in the document Functional description
of PRxx2 series controllers as well as in PR Master User Manual, which are available at
www.roger.pl.
4.4 Firmware update
The latest versions of firmware and Roger ISP software are available at www.roger.pl. In order to
update firmware it is necessary to connect the device by means of RS485 bus to communication
interface (UT-2USB or RUD-1) and then connect the interface to PC with installed Roger ISP
software. It is not necessary to disconnect the controller from access control system, it is only
required to place FDM jumper in order to put the device in firmware download mode. Therefore