Stability
Over Time: 0.1% of range ±1 digit for 6 months.
Overload Limitation
666 mA.
Update Period
750 ms.
Response Time
Responds to changes in input within a maximum of two update
periods. If the filter is activated, then the display responds to the
change within nine update periods.
Humidity Limitation
0 to 95% non-condensing relative humidity.
Power Interrupt
All configuration and calibration constants are stored in EEPROM
memory and are not affected by power loss.
Failure Mode
LCD meter failure will not affect transmitter operation.
Under/Over Range Indication
Input current < 3.5 mA: Display blank.
Input current > 22.0 mA: Display flashes 112.5% of full scale
value or 9999, whichever is less.
Hazardous Locations
Approved for use with Rosemount Models 444, 751, 1135, 1144,
and 1151.
Meter Size
2
1
/4-inch diameter face with
1
/2-inch high characters.