The Remote Hand Station provides a remote mountable display
which allows the operator to monitor and control an actuator
mounted in an inaccessible location. All operations which
could be performed at the actuator will be duplicated at the
Remote Hand Station, including configuration setup, data log
download and local control operation.
In order to use the RHS for control, the selectors on both the
actuator and RHS have to be set according to the table below:
7 - Operating the Remote Hand Station
ACTUATOR SELECTORS (HIGH PRIORITY)
REMOTE HAND
STATION SELECTORS
ACTUATOR CONTROL
Local Local
Actuator*
Local
Remote
Actuator*
Remote Local Remote Station
Remote Remote
Remote control through option cards or hardwired
control via terminal block.
* Actuator remains in control unless the Local mode is enabled.
When Local mode enabled, the RHS shares control despite the actuator set for Local Control. Refer to section 6.4
Functional operation and setup of the actuator via the RHS
mimics the actuator’s standard operation, refer to publications
PUB002-039 (safe use and installation) and PUB002-040 (full
configuration).
The connected actuator’s datalogger can be viewed and
extracted via the RHS. For datalogger extraction, please refer to
the Rotork Bluetooth
®
Setting Tool Pro manual PUB095-001.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the rotork IQ3 Range and is the answer not in the manual?

rotork IQ3 Range Specifications

General IconGeneral
Brandrotork
ModelIQ3 Range
CategoryControl Unit
LanguageEnglish

Related product manuals