EasyManua.ls Logo

rotork IQ3 Range - Approvals

rotork IQ3 Range
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A4 US
US
A4
US
A4
A4 US
11
Redefining Flow Control
Refer to RHS nameplate for unit specific approval details.
European – Hazardous Area
ATEX (94/9/EC) II 2 GD
Ex db IIB T4 Gb
Ex tb IIIC T120 °C Db T4, IP66 & IP68
Temperature -20 °C to +70 °C (-4 °F to +158 °F)
*Option -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (-58 °F to +104 °F)
Ex db IIC T4 Gb T4
Ex tb IIIC T120 °C Db T4, IP66 & IP68
Temperature -20 °C to +70 °C (-4 °F to +158 °F)
*Option -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (-58 °F to +104 °F)
International – Hazardous Area
IECEx. IEC60079-0 & IEC600679-1
Ex db IIB T4 Gb
Ex tb IIIC T120 °C Db T4, IP66 & IP68
Temperature -20 °C to +70 °C (-4 °F to +158 °F)
*Option -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (- 58 °F to +104 °F)
Ex db IIC T4 Gb T4
Ex tb IIIC T120 °C Db T4, IP66 & IP68
Temperature -20 °C to +70 °C (-4 °F to +158 °F)
*Option -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +70 °C (-58 °F to +158 °F)
USA – Hazardous Area
CSAUS - Explosionproof to NEC Article 500 (FM3615 & FM3616)
Class I, Division 1, Groups C & D
Class II, Division 1, Groups E, F & G
FM Explosionproof to NEC Article 500
FM3600, FM3615 & FM3616
Temperature -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (-58 °F to +104 °F)
Class I, Division 1, Groups B, C & D
Class II, Division 1, Groups E, F & G
Temperature -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (-58 °F to +104 °F)
Canada – Hazardous Area
CSA Explosionproof to C22.2 No. 30
CSA Dust explosionproof to C22.2 No. 25
Class I, Division 1, Groups C & D
Class II, Division 1, Groups E, F & G
Temperature -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (-58 °F to +104 °F)
Class I, Division 1, Groups B, C & D
Class II, Division 1, Groups E, F & G
Temperature -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (-58 °F to +104 °F)
International Non Hazardous
Watertight, BS EN60529
IP66 & IP68, (7 metres for 72 hours)
Temperature -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (-58 °F to +104 °F)
US – Non Hazardous
UL50 Enclosure Type 4x & 6
Temperature -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (-58 °F to +104 °F)
Canada – Non Hazardous
Enclosure Type 4x & 6 CSA C22.2 No. 94
Temperature -30 °C to +70 °C (-22 °F to +158 °F)
*Option -40 °C to +70 °C (-40 °F to +158 °F)
*Option -50 °C to +40 °C (-58 °F to +104 °F)
Rotork can supply RHS product to national standards not
listed above. For details please contact Rotork.
8 - Approvals