RTK Series UC625 Annunciator
41
Alarm Card Input Response Settings STANDARD VERSIONS
On standard versions of the UC625 Annunciator Switch SW1 & SW2 are used to set the response
time for each channel as detailed below.
ASIC version AS5317 is used on standard versions.
SW1
21 73 4 65 8
CH1 CH2
ON
CHANNEL
SWITCH
5MS
25MS
50MS
100MS
1
SW1-S1
ON
OFF
OFF
OFF
SW1-S2
OFF
ON
OFF
OFF
SW1-S3
OFF
OFF
ON
OFF
CHANNEL
SWITCH
5MS
25MS
50MS
100MS
2
SW1-S5
ON
OFF
OFF
OFF
SW1-S6
OFF
ON
OFF
OFF
SW1-S7
OFF
OFF
ON
OFF
21 73 4 65 8
ON
SW2
CH3 CH4
CHANNEL
SWITCH
5MS
25MS
50MS
100MS
3
SW2-S1
ON
OFF
OFF
OFF
SW2-S2
OFF
ON
OFF
OFF
SW2-S3
OFF
OFF
ON
OFF
CHANNEL
SWITCH
5MS
25MS
50MS
100MS
4
SW2-S5
ON
OFF
OFF
OFF
SW2-S6
OFF
ON
OFF
OFF
SW2-S7
OFF
OFF
ON
OFF
Switches SW1-S4, SW1-S8, SW2-S4 and SW2-S8 are not used
Table 27