42
Alarm Card Input Response Settings M3 / M4 OPTION VERSIONS
If specified at the time of order the UC625 Annunciator can be supplied with alternative response time
settings as shown below. Suffix Code M3 or M4 in the Model No is used to signify that the alternative
response times are available. Switch SW1 & SW2 are used to set the response time for each channel
as detailed below
ASIC version AS6454 is used on M3 / M4 versions.
SW1
21 73 4 65 8
CH1 CH2
ON
CHANNEL
SWITCH
5MS
25MS
200MS
5S
1
SW1-S1
ON
OFF
OFF
OFF
SW1-S2
OFF
ON
OFF
OFF
SW1-S3
OFF
OFF
ON
OFF
CHANNEL
SWITCH
5MS
25MS
200MS
5S
2
SW1-S5
ON
OFF
OFF
OFF
SW1-S6
OFF
ON
OFF
OFF
SW1-S7
OFF
OFF
ON
OFF
21 73 4 65 8
ON
SW2
CH3 CH4
CHANNEL
SWITCH
5MS
25MS
200MS
5S
3
SW2-S1
ON
OFF
OFF
OFF
SW2-S2
OFF
ON
OFF
OFF
SW2-S3
OFF
OFF
ON
OFF
CHANNEL
SWITCH
5MS
25MS
200MS
5S
4
SW2-S5
ON
OFF
OFF
OFF
SW2-S6
OFF
ON
OFF
OFF
SW2-S7
OFF
OFF
ON
OFF
Switches SW1-S4, SW1-S8, SW2-S4 and SW2-S8 are not used